The brand new 5103 Series instrument can measure insulation resistance, AC voltage and phase sequence. As a new generation all mighty electrical test instrument we have successfully developed recently it has made fundamental changes to the circuit industry of conventional insulation resistance Aided by the nice and fashionable design, have more and stronger functions are easier to use and more reliable The instrument and accessories are all in the toolbox fit for field application It can be used to test the insulation resistance of power system electrical equipment lightning arrester equipment and measure AC voltage and phase sequence test.
Panel introduction
1. LCD display
2. Phase sequence measurement LED indicators (CW, CCW, L1, L2 and L3)
3. Insulation resistance measurement high voltage LED indicator
4. Data holding switch
5. Test button
6. Backlight indicator switch
7. Function switch
8. ACV Input terminal
9. LINE input terminal Insulation
10. EARTH input terminal Insulation
11. Phase sequence L input terminal
12. Phase sequence L2 input terminal
13. Phase sequence L3/ACV measurement Gterminal shield input terminal for insulation
Performance Features
1. Low power consuming CMOS dual integral A/D conversion IC, automatic zero
2. LCD: 3 1/2 bit large screen display, maximum reading 1999
3. Data holding function, functional icons display
4. Can measure voltage lower than AC600V
5. Low Battery indication
6. LCD backlight function
7. Can test phase sequence
8. Automatically convert range Insulation test only
9. Perfect protection circuits, which can effectively prevent the harm of reverse voltage
10. LCD dimension: (65x48)mm (digit is mm high
11. Power: 8x1.5V (R6 AA) battery
12. Dimension: 190x155x75mm
13. Weight: approximately 900g
14. The instrument and accessories can be put into one for easy carriage
15. Environment conditions
16. Operating temperature: 0℃~40℃
Relative humidity<80%
Storage temperature: -10℃ ~50℃
Relative humidity<80%
1. Insulation Resistance
MODEI |
DY5103A |
Testing Voltage |
1000/2500/5000V |
Out Voltage |
90%-110% of the test voltage |
Range |
0.1MΩ-200GΩ |
Resolution |
0.01MΩ |
Accuracy |
0.1MΩ-200MΩ±(3%rdg+5dgt) |
200MΩ-10GΩ±(5%rdg+5dgt) |
|
10GΩ-200gΩ±(10%rdg+5dgt) |
2. AC Voltage Measurement
Measurement range: 0-600V
Accuracy: 2% rdg+5dgt
Resolution:1V
Test frequency: 50/60Hz
3. Phase Sequence Test
Phase-phase voltage range tested: 100V-450V
Frequency tested: 40-60Hz
①The phase sequence function allows you to test the phase sequence of 3-phase AC power supply (100V- 450V/40-60Hz). When you have connected the phase sequence probes with the test wires by input terminals you can judge the positive phase and reverse phase of phase AC according to LED indicator and beep, and phase missing indicated by LED
②Test State
Phase Sequence Test Indication |
Open Phase Test Indication
|
Beep
|
Positive phase (CW indicator is on)
|
L1, L2 and L3 indicators are on.
|
Long beep
|
Reverse phase (CCW indicator is on)
|
L1, L2 and L3 indicators are on
|
No beep
|
Missing phase (CCW indicator is on)
|
Any of L1, L2 and L3 is not on
|
No beep
|
Note: When the measurement probes have been connected, the phase sequence measurement function shall indicate the positive phases and reverse phases of a 3-phase AC, and the LED indicator will indicate the phase missing. Be sure to measure with 3 triple-color test wires with 3 round crocodile clamps
4. Phase Sequence test result is indicated by LED No and display in LCD
Accessories
A host *1 (DY5103A)
a user manual *1(English)
toolbox *1
2 sets of dedicated test wires (a phase sequence test wire, an insulation resistance test wire)
8 cells of 1.5V AA batteries(not including)